Description
Water Cooling (+WC) is available for Magna-Power power supplies to enable high-power density in cabinets where heat removal via standard air cooling is a challenge.
Water cooling is accomplished with chill plates and an integrated central heat exchanger. The chill plates provide a thermal conduction path for heat-sensitive components, while the central heat exchanger removes heat from the air internal to the enclosure. 1U, 3U, 6U and 9U water-cooled models feature enclosures without vent holes and are essentially sealed from the environment. An internal solenoid valve enables water flow only when the chill plate reaches 60°C; this operation prevents internal condensation.
Plumbing and Connections
1U SLx Series as well as 3U and 4U TS Series models utilize a 1/4" NPT male inlet and outlet for water flow. For 6U, 8U, 12U and 16U TS Series, external plumbing interconnects power supply modules to a single 1/2” NPT male connection for the inlet and another for the outlet.
A minimum of 2.5" of clearance is recommended behind the enclosure for plumbing hardware and user connections. For systems requiring more than one power supply, plumbing connections must be paralleled; water should not flow from one power supply into another. When water-cooled power supplies are ordered with the Cabinet and Integration accessory, Magna-Power will parallel these connections, providing a single inlet and outlet for the entire rack.
Note: The Water Cooling (+WC) option cannot be combined with the High Isolation Output (+ISO) option. On the TS Series, the Water Cooling (+WC) option is only available for models rated up to 1000 Vdc.
Water Cooling Specifications
| Series | Model Size | Min. Flow Rate | Pipe Size (NPT Male) | Max. Pressure | Max. Inlet Temp |
|---|---|---|---|---|---|
| SLx Series | 1U | 1.2 GPM | 1/4” | 80 PSI | 25°C |
| TS Series | 3U, 4U | 1.5 GPM | 1/4” | 80 PSI | 25°C |
| TS Series | 6U, 8U | 3.0 GPM | 1/2” | 80 PSI | 25°C |
| TS Series | 9U, 12U | 4.5 GPM | 1/2” | 80 PSI | 25°C |
| TS Series | 16U | 6.0 GPM | 1/2” | 80 PSI | 25°C |
*Front air intake and rear exhaust applicable to 6U through 16U models only.